1.1. Verify that cabinets or cutout boxes are suitable and properly installed in any wet or damp locations.
1.2. Verify that cabinets in walls do not have excessive gaps at the edges and are flush with the finished surface or, if surfaces are noncombustible, within 1⁄4 in. (6 mm) of the finished surface.
1.3. Check for closure of conductor openings.
1.4. Verify that cables are secured to cabinets and cutout boxes or that the conditions for cables with nonmetallic sheaths are met.
1.5. Check wiring and bending space in cabinets and cutout boxes.
1.6. Check cabinets and cutout boxes for adequate space for conductors and for splices and taps where they exist.